格力空调故障代码\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a KF-60L WAK分体立柜式房间空调器故障代码:\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E1 1、冷凝器前有障碍物\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 2、控制回路巽常\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 3、室外环境温度高于43度时开始制冷\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 4、高压管压力过大使高压开关动作\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E2 1、室内风机不转或风口堵住\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 2、室内环境温度低于18度\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 3、管温感温头折断\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 4、管温感温头插头没插好\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 5、控制回路巽常\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 6、电容C7漏电\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a LF-12WAK分体立柜式房间空调器故障代码:\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E1 1、冷凝器前有障碍物\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 2、控制回路巽常\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 3、三相电源缺相\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 3、室外环境温度高于43度时开始制冷\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 4、工作电流过大使过护器动作或高压管压力过大使高压开关动作\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E2 1、室内风机不转或风口堵住\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 2、室内环境温度低于18度\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 3、管温感温头折断\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 4、管温感温头插头没插好\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 5、控制回路巽常\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 6、电容C7漏电\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 格力:变频柜机E1-E5\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E1:压机过流,过热,排气过高,模块保护;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E2:室内防冻结保护;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E3:室内温度感温包开,短路;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E4:室内管温开,短路;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E5:室内外通讯故障。\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a :定频机故障代码:\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E1:压缩机高压保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E2:蒸发器防冻结保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E3:压缩机低压保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E4:压缩机排气温度过高保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E5:过电流(低电压保护)\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 格力空调维修数据\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 一:格力定频机器挂机的传感器的阻值比较小,也就是说比较精确,不过也是最容易坏的!常见故障就不说了!说2个不好查的:1制冷时20分钟左右压机停;2制热外风机不工作;很大可能都是室内管温问题![适用所有定频机]\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 二:普通分体机,1:就是带灯箱的E1表现为一开机立刻停,除灯箱可以开以外别的功能都没有用。[简单解决方法:将控制板的OVC线与零线短接,仍是E1为控制板坏,不显示E1那就是高压保护开关等断开]2:E3故障有的机器根本就没有低压保护开关,可是换了所有控制元件还是解决不了问题,原来是现在的很多控制板都是通用的,只要把控制板上的LPP线与零线短接就可以了!\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 三:变频冷静王维修资料\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 1 排气温度保护:当T排气高于115度时,压机停,小于90度压机停已达三分钟后恢复运行;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 2 防冻结保护:当T内管小于-1度,压机停,大于6度压机停已达三分钟恢复运行;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 3 过电流保护:当I总大于D时,压机停,外风机30秒停\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 制冷时32机D=10A,25机D=8A;制热时32机D=13A,25机D=10A\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 4 过负荷保护:当T管大于62度时,内风机按设定风速运行,压机停。\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a T管:制冷时是室外热交换器温度,制热时是室内热交换器温度。\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 5 室内,外故障显示:D1,D2,D3为内机灯,LED1[绿灯]LED2[红灯]LED3[黄灯]为外机灯。\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a A压机停且有故障时LED1亮;B室外环境温度有故障时LED3亮;C室外管温有故障时LED2亮;D模块保护时LED1闪烁;E压机过载时LED2与LED3同时闪烁;F排气温度有故障时LED1,LED2,LED3全亮;G室内D1压机运行时亮;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a H室内D2时通讯指示,正常时闪烁;I室内D3是感温包指示灯,有故障时闪烁。\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 6 功率模快:各线功能\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 1号线:W相的负端控制信号;2号线:W的正端控制信号;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 3号线:V的负端控制信号;4号线:V正端控制信号;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 5号线:U的负端控制信号;6号线:U正端控制信号;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 7号线:地线;8号线;+5V线;9号线:+12V线;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 10号线:模块保护信号线[模块保护有:过热,过流,欠压保护,保护时模块有微秒极的信号输出]\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a 四:变频柜机E1-E5\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E1:压机过流,过热,排气过高,模块保护;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E2:室内防冻结保护;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E3:室内温度感温包开,短路;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E4:室内管温开,短路;\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E5:室内外通讯故障。五:定频机故障代码:\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E1:压缩机高压保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E2:蒸发器防冻结保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E3:压缩机低压保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E4:压缩机排气温度过高保护\\\\\\\\\\\\\\\\x0d\\\\\\\\\\\\\\\\x0a E5:过电流(低电压保护)
格力空调E1故障是原因:
从故障代码表查寻可得知,格力空调故障代码e1告警,是格力空调其中的故障代码,是电流过大保护作用的;包括压缩机电流过大保护,压缩机过热保护,室外机排气温度过高保护,室外机相序电流保护电路板坏。检测得知:室外机积太多尘土,太脏倒至空调过热保护的原因。
故障分析:
在这就把格力KF-72LW(72332)-R-N5机型出现E1告警所有问题全部列出:
1、氟利昂多引起高压保护器动作(断开)。
2、该机使用的时间过长,制冷系统内部有泄漏处理完后常加冷剂或更换过压缩机不注意,脏物入进制冷系统引起毛细管堵塞不能达到节流、降温、降压作用。倒至空调器高压压力过高、低压压力过低,压力保护器动作(断开)。
3、室外风机坏(注:风机启动电容坏,风机也是不动转),不转,倒至保护器动作(断开)。
4、室外机相序电流保护电路板坏
5、室外机凝器积太多尘土、太脏倒至空调过热保护
空调故障检测排除:
经过检测,空调器制冷时用压力表测量低压压力过高为0.75 Mpa(0.5~0.6 Mpa),停机后平衡压力为0.9Mpa(表示系统里氟利昂不多不少)。
E1故障空调处理过程:
清洗干净空调室外机冷凝器,试机正常,故障处理完毕!
以上就是格力空调E1故障代码处理的方法,更多格力空调故障代码请参考:南宁粒勤家电,更多免费的视频教程,精彩内容等你哦。
格力空调E1:高压保护
主要原因:
1、线路问题
2、主板问题
3、保护器本身问题
开机工作一段时间出现E1
1、室外冷凝器脏
2、制冷剂过多
3、电流过大
建议你先自己好好的清洗一下外机的散热片即可!
如果清洗后仍不能解决、建议你找厂家给检查吧!
E1是系统高压保护,具体故障原因需要格力服务人员上门检测处理。请您点击这里或联系格力全国统一客户服务热线4008-365-315进行服务预约。